Description
Intelligent Wireless Modules
Triga wireless modules are intelligent addressable modules which provide secure, reliable communication to the Fire Alarm Control Panel (FACP) across a Class A mesh network. Wireless modules create an opportunity for applications where it is costly (concrete walls/ceilings, buried wires), obtrusive (surface mount conduit), or possibly dangerous (asbestos) to use traditional wired devices. In addition, both wired and wireless devices can be present on the same FACP providing an integrated wired-wireless solution for increased installation potential.
The mesh network within the Triga system creates a childparent relationship between the devices so that each device has two parents providing a second path for communications on every device. If one device can no longer operate for any reason, the rest of the devices can still communicate with each other, directly or through one or more intermediate devices.
The Triga system also engages frequency hopping to prevent system interference whether intentional or accidental. The Triga monitor module is intended for use with a wireless gateway to interface with a device having contacts used to signal status conditions. It is designed to provid an interface to contact devices such as security contacts, waterflow switches, or pull stations. The input to the monitor module is non-latching and does not require a reset. The device has a panel controlled LED indicator. The monitor module must be within 3- feet of the monitored device when using field wiring or 20 feet in nonmetallic conduit.
The Triga relay module allows a compatible control panel to switch discrete contacts by code command. The relay contains an isolated set of Form-C contacts, which operate as a SPDT switch. Circuit connections to the relay are not supervised by the module. The Triga relay module can be used to activate functions such as a remote power supply
TRW-RELAY WIRELESS RELAY MODULE
(in conjunction with a monitor module), elevator recall, door holders and fan shutdown of wired devices or Triga devices within the same mesh network. The module also includes a panel-controlled LED indicator.
The devices communicate across the mesh network through a gateway to the FACP. The FACP views the Triga wireless device and another addressable device on the system providing similar detection functions and outputs as a wired counterpart. In addition, both wired and wireless devices can be present on the same FACP to meet the needs of a given application. A Triga wireless system can use any combination of modules, smoke, or heat detectors.